Specification Foamed-in-Place Insulation SECTION 07240 FOAMED-IN-PLACE INSULATION PART 1 -GENERAL 1.01 SUMMARY: A. Section includes: Providing foamed-in-place insulation installed in stud walls, masonry cavity walls, or concrete unit masonry cores as indicated. B. Related sections: 1. Section 04210: Brick Unit Masonry. 2. Section 04220: Concrete Unit Masonry. 3. Section 04221: Architectural Concrete Unit Masonry. 4. Section 09260: Gypsum Board Systems. 1.02 REFERENCES: A. Standards of the following as referenced: 1. American Society for Testing and Materials (ASTM). 1.03 DEFINITIONS: A Terms: 1. ACMU : Architectural Concrete Masonry Unit . 2. CMU: Concrete Masonry Unit. 1.04
SYSTEM DESCRIPTION:
A. Performance requirements:
1. Meet Factory Mutual Systems, Class A rating when tested in accord with
ASTM E84-86.
2. Water vapor transmission: 15.5 to 16.9 perms-in when tested in accord with
ASTM C355-84.
3. Surface burning characteristics when tested in accord with ASTM E84-86.
a. Flame Spread = 5
b. Smoke Development = 0
c. Fuel Contribution = 0
4. Thermal performance:
a. K-factor at 75 deg. F: 0.22
b. R-value: 4.9 @ 32°F per inch thickness, nominal.
5. Shrinkage: .5 percent to 1.5 percent.
6. Electrical Conductivity Tests performed on wet and dry foamed samples.
7. Heat of Combustion ASTM D-240-73 - not to exceed 7,000 BTU's per pound.
1.05
SUBMITTALS
A. Product data: Submit complete data indicating compliance with specified requirement.
B. Quality control submittals:
1. Test reports: Submit indicating compliance with Article 1.04.
1.06
QUALITY ASSURANCE:
A Qualifications:
1. Installer: Certified and trained by manufacturer with a minimum of 3 years
direct experience in the use of the Tripolymer product specified.
B. Certifications:
1. Certify material use no CFC's (chlorofluorocarbon) in chemical formulation
or installed product.
2. Materials contains no asbestos.
3. Certify material is a phenolic base co-polymer (non-urea formaldehyde).
1.07 DELIVERY, STORAGE. AND HANDLING: A. Packing and shipping: 1. Pack to protect from breakage and damage in shipping. 2. Provide materials in original unopened containers with manufacturer's labels intact and legible. B. Acceptance at site: 1. Unload materials; check for damage. 2. Open. punctured. or opened damaged containers will not be accepted. 3. Damaged materials determined from by visual inspection will not be accepted. 4. Remove rejected materials from site immediately. C. Storage and protection: 1. Store materials in dry area in manufacturer's protective packaging in original containers with labels and installation instructions intact. 2. Protect materials from freezing. Part 2 -Products
2.01
Materials:
A. Acceptable products: C.P. Chemical Company, Inc., Tripolymer 105 or Tripolymer C.M.U.
Foam-in-Place Insulation
B. Characteristic:
1. Type: Foamed-in-place phenol methylene interconnected co-polymer.
2. R Value:
a. Interior wood frame walls: R-as specified: STC rating as specified
b. Interior steel frame walls: R-as specified: STC rating as specified
c. Cavity wall: R-as specified
d. Masonry core: R-as specified
Part 3 -Execution 3.01 PREPARATION: A. Protection of construction activities specified in this section: 1. Protect partially completed or completed walls not being worked on with waterproof membrane until work of other trades completes protection of walls. Coordinate with construction activities specified in **Brick Unit Masonry** or** Architectural Concrete Unit Masonry** or** Concrete Unit Masonry sections . 2. Overhang wall at least 1'6" on each side of wall with covering; anchor on each side of wall. Provide cover of sufficient durability to withstand wind and rain. 3.02 INSTALLATION: A. Cavity wall: Install foam insulation in cavity between masonry wythes full thickness of cavity in fills not exceeding 15' -0" height as masonry walls are constructed in accord with manufacturer's installation instructions. B. Frame construction: Install foam insulation where indicated to thickness required for indicated R-Value~ or STC rating, install in accord with manufacturer's installation instructions. C. Core fill: 1. Install foam insulation in masonry cores full thickness, fills not exceeding 15'-0" height as masonry walls are constructed in accord with manufacturer's installation instructions, -OR- 2. Drill holes in C.M.U. face shell or in mortar joint around entire wall area
approximatelyfive feet (5ft) from floor level. Repeat at height no greater than
fifteen feet (15 ft) in vertical height until completion of wall area fill cores completely
with foam insulation. Patch holes flush to match adjacent material.
END OF SECTION 07213 |
|